7.8003.14a
Assessment Lighting strategy will be provided by lighting professional
Work order will be evaluated against site circumstances
Determine and ensure appropriate device and location
7.8003.14b
Selection Hard-wired indoor fixtures will be in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
UL
UL
Underwriters Laboratories
1598
Plug-in indoor fixtures will be in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
UL
UL
Underwriters Laboratories
153
Hard-wired outdoor fixtures will be suitable for local climatic conditions and in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
UL
UL
Underwriters Laboratories
product standards
Fixture will be capable of being attached to existing wiring
Fixture will carry at least a 1-year warranty
Test existing emergency fixtures and repair or replace if necessary
In-unit replacement fixtures will be ENERGY STARĀ® qualified
Fixture will comply with selection criteria of SWS 7.8003.11 Lamp Replacement and SWS 7.8003.13 Ballast Replacement
Reduce energy use
Ensure device functions appropriately
Ensure product safety
Ensure occupant safety
7.8003.14c
Installation Work will be performed by licensed electrical professional or a qualified contractor
Fixture will be de-energized before work begins
Appropriate lockout procedures will be followed in accordance with
OSHA
OSHA
U.S. Occupational Safety and Health Administration, www.osha.gov
1910 Subpart S and
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
70E
Fixture will be installed in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
70,
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
70E, and manufacturer specifications
All penetrations will be sealed (
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
/
ICC
ICC
International Code Council
Fire Code)
Egress fixtures will be installed in accordance with applicable codes (
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
101)
Lighting fixtures will be installed and secured as specified NECA/IESNA 500
Ensure worker safety
Ensure occupant safety
Preserve integrity of building
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
Ensure integrity of fire barrier
Ensure quality installation
7.8003.14d
Commissioning Fixtures will be tested to meet IESNA light levels for certain tasks
Fixtures will not impact required egress lighting, as required by
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
101
Meet target light levels
Ensure occupant satisfaction
Ensure occupant safety
7.8003.14e
Decommissioning Fixtures, lamps, and ballasts will be disposed of in accordance with local ordinances or manufacturer specifications
Ballast manufacture date will be determined, if possible
If the ballast is known to contain PCBs, does not have "No PCBs" on the ballast, or if the manufacturer cannot determine if the ballast contains PCBs, assume the ballast contains PCBs and dispose of ballast in an
EPA
EPA
U.S. Environmental Protection Agency, www.epa.gov
-approved facility
Ballasts manufactured in 1979 and after will be disposed of in accordance with local ordinances or manufacturer specifications
Protect the environment
Prevent the reuse of inefficient components
7.8003.14f
Safety Broken lamps containing mercury will be cleaned in accordance with
EPA
EPA
U.S. Environmental Protection Agency, www.epa.gov
guidelines
Ensure worker safety
Ensure occupant safety
7.8003.14g
Staff education Building operations staff will be provided with warranty information, product specification, and installer contact information
Educate building operations staff about operation and maintenance of equipment
Ensure continued savings
7.8003.14h
Occupant education Occupants will be educated on new fixtures and benefits
Occupants will be provided with lamp disposal procedure, as determined by building operations staff
If lamps containing mercury are used, occupants will be provided with lamp disposal procedure in accordance with
EPA
EPA
U.S. Environmental Protection Agency, www.epa.gov
guidelines
Education will be provided by building operations staff
Educate occupants about new fixtures and benefits
Ensure continued savings
Protect the environment
Ensure occupant safety