6.6202.6a
Equipment specifications Specifications will be field verified as appropriate to site conditions by installer
Ensure appropriate equipment is specified
Ensure design and installation are feasible
6.6202.6b
Air flow
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
62.2 and local code requirements should be followed for identifying design airflow rates within apartment dwelling units.
All other areas will follow local code requirements and/or
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
62.1 requirements
Air flows will be measured in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5 or
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 111 and adjusted to meet design requirements
Provide sufficient outdoor air to desired locations
6.6202.6c
Wiring Wiring will be installed by a properly licensed contractor
Wiring will be installed in accordance with original equipment manufacturer specifications, and local and national electrical and mechanical codes
Refer to
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
70: National Electrical Code for installation requirements
Prevent an electrical hazard
6.6202.6d
Access Fans,
service switch
Service switch
An electrical switch that controls the complete flow of electricity to a mechanical device
, filters, drain, and drain pan will be accessible for maintenance or replacement
Maintain designed air flows and system performance
Ensure occupant health and safety
6.6202.6e
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
mounting Fan will be mounted securely in accordance with manufacturer specifications and local code requirements (in terms of seismic restraints)
Fan will be oriented so the equivalent length of the duct run is as short as possible
Fan will be isolated from the building framing unless specifically designed to be directly attached
Ensure short duct runs achieve optimum air flows
Ensure fan is mounted securely
Ensure fan housing or building framing does not shake, rattle, or hum when operating
Minimize noise
6.6202.6f
Condensate drain Condensation shall be drained to a location approved by the local jurisdiction
Prevent moisture problems
6.6202.6g
Backdraft dampers (required for intermittent operation) A
backdraft damper
Backdraft damper
A damper that allows air to flow in only one direction
will be installed between the
HRV
HRV
Heat recovery ventilator
or
ERV
ERV
Energy recovery ventilator
and the exterior, unless the system operates continuously
Prevent reverse air flow when the system is off
6.6202.6h
Fan outlet termination Minimum distance of exhaust outlet from any doors, windows, or outside air intakes shall be in conformance with the applicable building code
Outlet will be sealed to prevent water intrusion and exhaust air leakage into building cavities
Direct exhaust to the outdoors and prevent re-entry
Prevent entry of weather and pests into building shell
Ensure occupant health and safety
6.6202.6i
Intake location Intake will be installed in accordance with the following:
A minimum of 6" above grade A minimum of 10' from contaminant sources Above local snow or flood line A minimum of 18" above an asphalt-based roof Minimum distance between exhaust outlet and air intake will be 6' or in accordance with manufacturer specifications
Ensure occupant health and safety
Prevent entry of contaminants
Ensure unrestricted airflow
6.6202.6j
Intake/exhaust fitting Intake/exhaust fitting will have integrated collar that is at least the same diameter as the duct
Fitting will be appropriate for regional weather conditions and installation location on exterior of building
Effectively draw the required volume of air from outside
Preserve integrity of the building
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
Ensure durable installation
6.6202.6k
Weatherproofing Exterior termination fittings will be flashed or weather sealed
Water will be directed away from penetration
Weatherproofing will be in accordance with manufacturer specifications
Prevent entry of weather into building shell
6.6202.6l
Pest exclusion Screen material no less than 1/4" and no greater than 1/2" hole size in any direction will be used at any exhaust and intake
Prevent entry of pests into building shell
6.6202.6m
Duct connections Ducts will be connected to applicable registers or grilles, collector box,
HRV
HRV
Heat recovery ventilator
or
ERV
ERV
Energy recovery ventilator
, intake fitting, and termination fitting
Ducts will be connected and sealed in accordance with duct exhaust and supply duct detail
Achieve the desired air flows to and from the desired locations
Preserve integrity of the duct system and building
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
6.6202.6n
Duct layout for attachment to forced air systems Exhaust air will not be taken from the forced air system
Outdoor air supply ducts attached to the return side of forced air systems will be:
Attached as close to the heating, ventilation, and air conditioning (
HVAC
HVAC
Heating, ventilation, and air conditioning
) system's fan as possible, while remaining in compliance with manufacturer specifications Connected to the outdoor air outlet from
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
system Filtration of ventilation air will be provided before reaching the
HVAC
HVAC
Heating, ventilation, and air conditioning
fan Connected and sealed in accordance with the supply duct detail Achieve the desired air flows to and from the desired locations
Preserve integrity of duct system and building
Ensure occupant health and safety
6.6202.6o
Duct layout for fully ducted
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
systems All ducts will be connected and sealed in accordance with SWS 6.6004.2 Individual Exhaust Fan Serving Multiple Rooms Within a Single Dwelling Unit and SWS 6.6102.7 Ducts for Supply
Achieve the desired air flows to and from the desired locations
Preserve integrity of duct system and building
Ensure occupant health and safety
6.6202.6p
Insulation Outdoor air intake duct will be insulated from the outdoor air intake to the
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
system to a minimum of R-8 or equivalent to local codes
Ducts installed outside of the thermal
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
will be insulated to a minimum of R-8 or equivalent to local codes
Preserve integrity of the duct system by eliminating condensation
6.6202.6q
Register boot to interior surface seal Register boot will be sealed to interior surfaces with sealants compatible to their intended surfaces
Sealants will be continuous and meet fire barrier specifications
Prevent air leakage around boot
Ensure a permanent seal to the building
air barrier
Air barrier
The separation between the interior and exterior environments of a building that slows air flow to the point that no smoke movement is visible at 50 pascals of pressure difference across the boundary
Prevent a fire hazard
6.6202.6r
Sealant selection Sealants will be compatible with their intended surfaces
Sealants will be continuous and meet fire barrier specifications
Ensure a permanent seal
Prevent a fire hazard
6.6202.6s
Balance and flow Air flows will be measured in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5 or
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 111 and adjusted to match to the design specification
Achieve the desired air flows to and from the desired locations
6.6202.6t
Fire dampers Fire dampers must be accessible for inspection and/or testing by the local authorities; if fire dampers are not accessible from a grill or register, an access door in the ductwork is required
Sealing activities will not interfere with the operation of fire dampers, balancing dampers, or backdraft dampers
Type B fire dampers will be used as required by fire code
Ensure access to fire dampers for safe operation
Minimize static pressure
Maximize air flow
6.6202.6u
Occupant/property manager education Occupant/property manager will be educated on purpose of system, and also how and when to change filter and clean drain pan, if applicable, in accordance with manufacturer specifications
Ensure occupant health and safety
Preserve integrity of system