6.6202.5a
Equipment specification Specifications will be field verified as appropriate to site conditions by installer
Ensure appropriate equipment is specified
Ensure design and installation are feasible
6.6202.5b
Air flow
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
62.2 and local code requirements should be followed for identifying design airflow rates within apartment dwelling units; all other areas will follow local code requirements and/or
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
62.1 requirements
Air flows will be measured in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5 or
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 111 and adjusted to meet design requirements
Provide sufficient outdoor air to desired locations
6.6202.5c
Wiring Wiring will be installed by a licensed contractor
Wiring will be installed in accordance with original equipment manufacturer specifications, and local and national electrical and mechanical codes
Refer to
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
70: National Electrical Code for installation requirements.
Prevent an electrical hazard
6.6202.5d
Access Fans,
service switch
Service switch
An electrical switch that controls the complete flow of electricity to a mechanical device
, filters, drain, and drain pan will be accessible for maintenance or replacement
Maintain designed air flows and system performance
Ensure occupant health and safety
6.6202.5e
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
mounting
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
will be mounted securely in accordance with manufacturer specifications and local code requirements (in terms of seismic restraints)
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
will be oriented so the equivalent length of the duct run is as short as possible
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
will be isolated from the building framing unless specifically designed to be directly attached
Ensure short duct runs achieve optimum air flows
Ensure
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
is mounted securely
Ensure
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
housing or building framing does not shake, rattle, or hum when operating
Minimize noise
6.6202.5f
Condensate drain Condensation shall be drained to a location approved by the local jurisdiction
Prevent moisture problems
6.6202.5g
New connecting ductwork All exposed ductwork outside of the building will be insulated to a minimum R-12, protected from weather exposure, and sealed at all penetrations into building shell
Ensure durability and energy efficiency of ductwork
6.6202.5h
Distribution systems Note:
HRV
HRV
Heat recovery ventilator
/
ERV
ERV
Energy recovery ventilator
provides the outdoor air supply fan and the exhaust fan
The rest of the ventilation system will be installed in accordance with the following details:
SWS 6.6104.1 Outdoor Supply Air Handling Unit Serving Multiple Dwelling Units or Corridors ) SWS 6.6004.1 Central/Common Exhaust Fan Serving Multiple Dwelling Units via Common Duct(s) and Dwelling Unit Branches Achieve the desired air flows to and from the desired locations
Preserve integrity of the duct system and building
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
6.6202.5i
Fire dampers Fire dampers must be accessible for inspection and/or testing by the local authorities; if fire dampers are not accessible from a grill or register, an access door in the ductwork is required
Sealing activities will not interfere with the operation of fire dampers, balancing dampers, or backdraft dampers
Type B fire dampers will be used as required by fire code
Ensure access to fire dampers for safe operation
Minimize static pressure
Maximize air flow
6.6202.5j
Occupant/property manager education Occupant/property manager will be educated on purpose of system, and how and when to change filter and clean drain pan, if applicable, in accordance with manufacturer specifications
Ensure occupant health and safety
Preserve integrity of system