| 6.6201.3a
Balancing pressure | An appropriate means of pressure balancing will be installed (e.g., transfer grilles, jumper ducts, individual room returns) No room will exceed +/- 3 pascals with reference to the outside with all interior doors closed and ventilation systems running Return airflow paths for residential space shall be designed in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
1 Manual D or equivalent Ducts for common areas shall be designed in accordance with
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
procedures or
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Manual Q | Ensure free flow of air between rooms Preserve integrity of the building
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
|