| 6.6102.7a
Duct design and configuration | Duct shall be designed in accordance with the applicable codes adopted by the jurisdiction | Effectively move the required volume of air |
| 6.6102.7b
Duct insulation | Ducts installed outside of the thermal
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
will be insulated to a minimum of R-8 or equivalent to local codes | Prevent moisture condensation |
| 6.6102.7d
Duct connections | Metal-to-metal or metal-to-PVC connections will be fastened with a minimum of three equally spaced screws Flexible duct-to-metal or flexible duct-to-PVC connections will be fastened with tie bands using a
tie band
Tie band
A strap, often made of nylon, that mechanically squeezes a flexible duct to a fitting. Must have a minimum performance temperature rating of 165° (per UL 181A-type test) and a minimum tensile strength rating of 50 pounds
tensioning tool Flexible duct between the cable tie and end of metal or PVC duct will be screwed PVC-to-PVC materials will be fastened with approved PVC cement Supply ducts attached to the return side of forced air systems will be: - Attached as close to the heating, ventilation, and air conditioning (
HVAC
HVAC
Heating, ventilation, and air conditioning
) system's fan as possible while remaining in compliance with manufacturer specifications
- Set up to provide filtration of outdoor ventilation air before reaching the
HVAC
HVAC
Heating, ventilation, and air conditioning
system
- Attached via a mechanically fastened take off collar
In addition to mechanical fasteners, air seal duct connections will be fastened with
UL
UL
Underwriters Laboratories
181B or 181B-M listed material All other duct connections shall be in conformance with the applicable code adopted by the jurisdiction | Effectively move the required volume of air Preserve integrity of the duct system and building
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
|
| 6.6102.7e
Duct materials | Flexible duct materials will be
UL
UL
Underwriters Laboratories
181 listed or Air Diffusion Council approved | Effectively move the required volume of air Preserve integrity of the duct system and building
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
|
| 6.6102.7f
Outdoor air intake location | Intake will be installed in accordance with all applicable code requirements and/or the most current version of
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
62.2 | Reduce opportunity for contaminants to enter the building through the ventilation system |