5.3003.41a
Combustion air Combustion supply/exhaust air opening will be in compliance with applicable
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
standard (
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
31 or
NFPA
NFPA
National Fire Protection Association, www.nfpa.org
54/
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
AGA
AGA
American Gas Association, www.aga.org
Z223.1) or applicable local code
Exhaust combustion products to the outdoors
Ensure building is not damaged
Protect workers and occupants from injury
5.3003.41b
Flue vent material selection Flue vent material will be selected to prevent flue gas freezing and/or corrosion (using double wall where necessary)
Cost-effective materials will be used when appropriate and allowable
Ensure durability of flue vent system
Ensure selected material is appropriate and cost-effective
5.3003.41c
Installation Venting systems will be installed considering proper material, pitch, common venting, chimney liner, clearance, total equivalent length, and termination in accordance with applicable code
Category I venting systems will be installed in accordance with applicable code
Category III and IV venting systems will be installed in accordance with manufacturer specifications
Termination will be located away from windows, doors, and walkways
Aesthetics and noise will be considered
Venting will be routed in the shortest and most direct path possible
Joints in the flue piping will be properly sealed to prevent flue gas and condensation leakage
Exhaust combustion products to the outdoors
Ensure building is not damaged
Protect workers and occupants from injury