5.3003.15a
Oil system: smoke test Smoke test will be conducted before any combustion testing is completed
Smoke spot reading will be in accordance with burner manufacturer specifications
Ensure equipment:
Operates as designed Operates safely Operates efficiently Is durable
5.3003.15c
Oil filter Filter will be present, clean, and leak free
Ensure equipment:
Operates as designed Operates safely Operates efficiently Is durable
5.3003.15d
Fuel pressure Measurement will be verified in accordance with manufacturer specifications
Ensure equipment:
Operates as designed Operates safely Operates efficiently Is durable
5.3003.15e
Oil system: steady state efficiency (
SSE
SSE
Steady state efficiency
) Measurement will be verified in accordance with manufacturer specifications
Ensure equipment:
Operates as designed Operates safely Operates efficiently Is durable
5.3003.15f
Net stack temperature Net stack temperature will be measured and verified in accordance with manufacturer specifications
Ensure equipment:
Operates as designed Operates safely Operates efficiently Is durable
5.3003.15g
Carbon dioxide (CO2)and oxygen (O2) Measurement will be verified in accordance with industry manuals (e.g., Testo, Bacharach)
Ensure equipment:
Operates as designed Operates safely Operates efficiently Is durable
5.3003.15h
Excess combustion air Excess air will be minimized in accordance with industry best practices
Ensure equipment:
Operates as designed Operates safely Operates efficiently Is durable
5.3003.15i
CO
CO
Carbon monoxide
in flue gas
CO
CO
Carbon monoxide
in the undiluted flue gas will be less than 400 ppm air-free
Ensure equipment:
Operates as designed Operates safely Operates efficiently Is durable
5.3003.15j
Testing/inspection holes All testing and inspection holes will be sealed as approved by the authority having jurisdiction
Ensure equipment: