5.3002.12a
Chiller installation Maximum weight of refrigerant in a single space will be in compliance with
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Refrigerant monitors will be installed in accordance with
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Refrigerant relief valve will be piped to the outdoors and have an alarm
Unit operational efficiencies will meet minimums as required by
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
90.1
Structure will be able to support the unit
Vibration isolators will be provided
Manufacturer requirements will be followed when alternative storage methods for cooling towers are used (e.g., ice storage, ice tanks)
Reduce vibration to a non-objectionable level
Ensure optimum performance
5.3002.12b
Chiller maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
Tubes will be checked annually Electrical check of system will be performed Manufacturer-recommended maintenance procedures will be performed Proper operation of leak detectors will be verified Refrigerant charge will be verified Ensure proper chiller maintenance
5.3002.12c
Chiller commissioning Unit discharge temperature will be verified as called for by control system in accordance with the design documents
Inlet and outlet temperatures to condenser will be maintained in accordance with the design documents
Noise level will be maintained to be within designed criteria
Safety switches will be verified to operate when unsafe conditions occur
Ensure optimum performance
5.3002.12d
Split system installation Condensate will be piped to a properly sized sanitary drain
Refrigerant type will be acceptable to the project type
Unit operational efficiencies will meet minimums as required by
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
90.1
Structure will be able to support the unit
Each unit will be installed with a properly trapped condensate drain in accordance with manufacturer specifications (some situations require a pump)
Primary heating of newly installed split systems will not be electric resistance heat
Smoke detectors will be installed on systems that are greater than 2,500 cubic feet per minute (
CFM
CFM
Cubic feet per minute
)
Appropriate lengths and elevations of refrigerant lines between condensing units and indoor coil will be used in accordance with manufacturer specifications
Proper location (e.g., property lines, windows, units, outside air intakes) and clearances will be maintained in accordance with manufacturer specifications
Environmental conditions will be considered when selecting and installing coils (e.g., special corrosion-protected units)
Ensure proper installation of split system
5.3002.12e
Split system maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
Filters will be replaced in accordance with manufacturer specifications
Annual cleaning of coil and drain pan will be performed
Condensate drains/traps will be inspected and verified operational
Proper operation of add-on equipment will be verified (e.g.,
UV
UV
Ultraviolet
, humidifier, electrostatic filter)
Ensure proper maintenance of system
5.3002.12f
Split system commissioning Proper operation of thermostats will be verified
Carbon dioxide (CO2) sensors will be calibrated
Proper operation of smoke alarms will be verified
Proper operation of mixed air damper will be verified
If present, proper operation of heating valve will be verified
Drains will be clear of debris and obstructions
Ensure optimum performance
5.3002.12g
Package system unit installation Economizer (if installed) will be located away from pollutant sources
Condensate will be piped to a properly sized sanitary drain
Type of refrigerant will be verified as acceptable to the project type
Economizer/power exhaust or relief dampers will be verified for proper function and operation
Unit operational efficiencies will meet minimums as required by
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
90.1
Structure will be able to support the unit
Each unit will be installed with a properly trapped condensate drain in accordance with manufacturer specifications (some situations require a pump)
New package systems will not have their primary heating be electric resistance heat
Unit will be installed with CO2 control in high occupancy spaces (demand control ventilation)
Smoke detectors will be installed on systems that are greater than 2,500
CFM
CFM
Cubic feet per minute
Proper location (e.g., property lines, windows, units, outside air intakes) and clearances will be maintained in accordance with manufacturer specifications
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
Minimize energy use
Minimize health concerns (e.g., Legionnaires' disease)
5.3002.12h
Package system unit maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
Filters will be replaced in accordance with manufacturer specifications If applicable, blower belt, sheaves replacement, and alignment will be verified If applicable, proper operation of the variable speed drive will be verified Annual cleaning of evaporator and condenser coils, condensate trap, and drain pan will be performed Proper operation of add-on equipment will be verified (e.g.,
UV
UV
Ultraviolet
, humidifier, electrostatic filter)
Environmental conditions will be considered when selecting and installing coils (e.g., special corrosion-protected units)
Ensure proper maintenance of equipment
5.3002.12i
Package system unit commissioning Before commissioning startup, test and balance reports will be provided
Thermostats or building automation control will be verified to be functioning properly
Properly working sequence of operations will be verified
Properly functioning outdoor air, return air, supply air, CO2, and enthalpy sensor will be verified (if installed)
Proper operation of mixed air damper will be verified
Proper operation of reversing valve will be verified in heat pump units
Drains will be clear of debris and obstructions
Proper operation of motorized dampers will be verified
In 3-phase units, the correct rotation of blower, condenser fans, and compressor will be verified
Correct voltage level coming into unit will be verified
Proper heating and cooling operation will be verified as in accordance with manufacturer specifications
In heat pumps, proper defrost cycle operation will be verified
Proper operation of safety switches will be verified
Ensure optimum performance
5.3002.12j
Variable refrigerant flow (VRF) installation Building electrical characteristics, such as voltage and phase, will be checked to ensure proper equipment is selected
Maximum weight of refrigerant in a single space will not exceed the maximum allowed by
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Total equivalent length of refrigerant piping will not exceed manufacturer rating
Proper location and clearances will be maintained in accordance with manufacturer specifications
Each unit will be installed with a condensate drain (some situations require a pump)
Wall-mounted thermostats will be used
Location of branch controller will be selected for non-occupied areas
Outdoor air ventilation filter will be present
Reduce noise
5.3002.12k
VRF maintenance Filters will be replaced in accordance with manufacturer specifications
Annual cleaning of indoor and outdoor coils will be performed
Environmental conditions will be considered when selecting and installing coils (e.g., special corrosion-protected units)
Ensure proper maintenance
5.3002.12l
VRF commissioning Thermostats will be verified to be functioning properly
If installed, operation of ventilation damper will be verified
Proper refrigerant charge will be verified
Power supply will be verified (single phase units supply power from the outdoor units to the indoor units)
Reduce total system cost
Ensure equipment operates at optimal efficiency
Ensure equipment durability
5.3002.12m
Ductless mini split installation System will be a ductless mini split and not a VRF system
Ductwork will not be installed
Building phase will be checked to ensure proper equipment is selected
Total equivalent length of refrigerant piping will not exceed manufacturer specifications
Proper location and clearances will be maintained in accordance with manufacturer specifications
Each unit will be installed with a condensate drain (some situations require a pump)
Wall-mounted thermostats will be used
Reduce total system cost
Ensure equipment operates at optimal efficiency
Ensure equipment durability
5.3002.12n
Ductless mini split maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
Filters will be replaced in accordance with manufacturer specifications Annual cleaning of indoor and outdoor coils will be performed Reduce total system cost
Ensure equipment operates at optimal efficiency
Ensure equipment durability
5.3002.12o
Ductless mini split commissioning Thermostats will be verified to be functioning properly
Ventilation damper will be operational if outside air ducting is available, and airflow will be adjusted to provide the proper amount
Reduce total system cost
Ensure equipment operates at optimal efficiency
Ensure equipment durability
5.3002.12p
Package terminal air conditioner (PTAC) or package terminal heat pump (PTHP) installation PTAC sleeve will be sealed to
envelope
Envelope
The separation between the interior and exterior environments of a building that includes a combination of air and thermal barrier
Condensate will be piped away from the building when required by manufacturer specifications
Ducted PTACs will be used for conditioning multiple rooms
Structure will be able to support the unit
PTAC will be selected with outdoor air intake unless other ventilation strategy is present
Each unit will be installed with a condensate drain (some situations require a pump)
Environmental conditions will be considered when selecting and installing coils (e.g., special corrosion-protected units)
Ensure equipment operates at optimal efficiency
Ensure equipment durability
5.3002.12q
PTAC or PTHP maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
Filters will be replaced in accordance with manufacturer specifications Drains will be clear of debris and obstructions Annual cleaning of coils will be performed Ensure equipment operates at optimal efficiency
Ensure equipment durability
5.3002.12r
PTAC or PTHP commissioning Thermostats will be verified to be functioning properly
Ventilation damper will be operational if outside air ducting is available
If present, proper operation of heating valve will be verified
Drains will be clear of debris and obstructions
Ensure equipment operates at optimal efficiency
Ensure equipment durability
5.3002.12s
Cooling towers installation Location of unit will minimize overspray and noise impact on neighboring properties
Overspray will not be directed toward air intakes
Structure will be able to support the unit
Vibration isolators will be provided
Elevation of tower will be selected in relation to the net positive suction head required at the pump and in accordance with manufacturer specifications
Appropriate drainage will be available in accordance with local code
Capacity control will be in accordance with the sequence of operations (e.g., two-speed or variable speed)
Manufacturer specifications will be followed when alternative storage methods are used (e.g., ice storage, ice tanks)
Environmental design conditions will account for sump heaters, water treatment requirements, conservation regulations, and possible restrictions of usage
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
Minimize energy usage
Minimize health concerns (e.g., Legionnaires' disease)
5.3002.12t
Cooling towers (rain water option) maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
Manufacturer-recommended maintenance procedures will be performed Media will be cleaned Strainers will be cleaned Motors and/or belts will be serviced Drains will be clear of debris and obstructions Water treatment levels will be maintained Debris will be cleaned from sump Annual cleaning of coils will be performed Structural supports will be checked Ensure equipment operates at optimal efficiency
Ensure durability of equipment
Minimize energy use
Minimize health concerns (e.g., Legionnaires' disease)
5.3002.12u
Cooling towers commissioning Unit installed to manufacturer specifications will be verified
Secondary overflow drain operation will be verified
Proper operation of make-up water level detector will be verified
If multitowers exist, proper operation of the equalizer line will be verified
If applicable, proper sump heater operation will be verified
Proper installation of water treatment will be verified
If rain water system is used, proper operation of controls will be verified
Proper installation of tower fill media will be verified
Capacity controls operating in accordance with the sequence of operations will be verified
If applicable, proper operation of submeter will be verified
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
Minimize energy use
Minimize health concerns (e.g., Legionnaires' disease)
5.3002.12v
Economizers installation Economizer, if installed, will be located away from pollutant sources
Need for economizer outdoor air damper will be determined in accordance with
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
90.1 minimum requirements or local code
Unit will be installed with carbon dioxide (CO2) control in high occupancy spaces (demand control ventilation)
If unit economizer is part of fire life safety function, it will be tested for proper operation and control
Economizer, power exhaust, or relief dampers will be verified for proper function and operation
Minimize health concerns
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
5.3002.12w
Economizers maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
CO2 and temperature/enthalpy sensors will be calibrated
Smoke detector operation will be verified
Proper motorized damper operation will be verified
Lubrication and damper linkage adjustments will be maintained
Minimize health concerns
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
5.3002.12x
Economizers commissioning Properly working sequence of operations will be verified based on manufacturer specifications
Proper operation of the outdoor air, return air, supply air, CO2, and enthalpy sensor will be verified based on manufacturers specifications
Proper operation of mixed air damper will be verified based on manufacturer specifications
Proper operation of motorized dampers will be verified based on manufacturer specifications
Smoke detector and CO2 sensor interaction with the damper will be verified based on manufacturer specifications
Pressure relief system will be verified as working when economizer is open
Minimize health concerns
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
5.3002.12y
Water source heat pump installation Condensate will be piped to a properly sized sanitary drain
Type of refrigerant will be acceptable to the project type
Unit operational efficiencies will meet minimums as required by
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
90.1
Structure will be able to support the unit
Each unit will be installed with a properly trapped condensate drain in accordance with manufacturer specifications (some situations require a pump)
Unit will be installed with CO2 control in high occupancy spaces (demand control ventilation)
Smoke detectors will be installed on systems that are greater than 2,500
CFM
CFM
Cubic feet per minute
Two-way valves will be installed that open when the thermostat calls for heating or cooling
Minimize health concerns
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
5.3002.12z
Water source heat pump maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
Filters will be replaced in accordance with manufacturer specifications
Annual cleaning of the coil and drain pan will be performed
Proper operation of add-on equipment will be verified (e.g.,
UV
UV
Ultraviolet
, humidifier, electrostatic filter)
Thermostats will be verified to be functioning properly
CO2 sensor will be calibrated
Smoke detector operation will be verified
Environmental conditions will be considered when selecting and installing coils (e.g., special corrosion-protected units)
Minimize health concerns
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
5.3002.12aa
Water source heat pump commissioning Thermostats will be verified to be functioning properly
Proper operation of mixed air damper will be verified
Proper operation of two-way valve will be verified
Drains will be clear of debris and obstructions
Minimize health concerns
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
5.3002.12ab
Fan coil units installation Four-pipe systems, where applicable, will be installed in order to take advantage of simultaneous heating and cooling
Condensate will be piped to a properly sized sanitary drain
Adequate structural support will be verified for unit
Each unit will be installed with a properly trapped condensate drain in accordance with manufacturer specifications (some situations require a pump)
Unit will be installed with CO2 control in high occupancy spaces (demand control ventilation)
Filtration minimum efficiency reporting value (
MERV
MERV
Minimum efficiency reporting value
) level will be appropriate for type of space and equipment
If the building operates with a pneumatic system, the following components will be serviced and maintained: air compressor, air dryer system, thermostats, actuators, receiver controllers, sensors, and miscellaneous components, such as pneumatic electric, electric pneumatic solenoid, and solenoid switches
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
Minimize energy usage
Minimize health concerns (e.g., Legionnaires' disease)
5.3002.12ac
Fan coil units maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
Filters will be replaced in accordance with manufacturer specifications
Annual cleaning of the coil and drain pan will be performed
Proper operation of add-on equipment will be verified (e.g.,
UV
UV
Ultraviolet
, humidifier, electrostatic filter)
Thermostats will be verified to be functioning properly
CO2 sensor will be calibrated
Smoke detector operation will be verified
Environmental conditions will be considered when selecting and installing coils (e.g., special corrosion-protected units)
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
Minimize energy use
Minimize health concerns (e.g., Legionnaires' disease)
5.3002.12ad
Fan coil units commissioning Thermostats will be verified to be functioning properly
If applicable, proper operation of heating and cooling valve will be verified
Drains will be clear of debris and obstructions
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
Minimize energy use
Minimize health concerns (e.g., Legionnaires' disease)
5.3002.12ae
Wall furnace installation Penetrations through exterior walls will be sealed with the appropriate air sealing material
Adequate structural support will be verified for unit
A carbon monoxide detector will be installed in the rooms where the wall furnace is located
Filtration
MERV
MERV
Minimum efficiency reporting value
level will be appropriate for type of space and equipment
Ensure occupant health and safety
Ensure system efficiency
5.3002.12af
Wall furnace maintenance Maintenance will be scheduled in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 180 Standard Practice for Inspection and Maintenance of Commercial Building
HVAC
HVAC
Heating, ventilation, and air conditioning
Systems
Maintenance procedures include, but are not limited to, the following:
Filters will be replaced in accordance with manufacturer specifications
Thermostats will be verified to be functioning properly
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
Minimize energy use
5.3002.12ag
Wall furnace commissioning Thermostats will be verified to be functioning properly
Filters will be verified to be clear of debris
Temperature rise will be within manufacturer specifications
Gas pressure will be within manufacturer specifications
A combustion analysis test will be performed and documented
Ensure equipment operates at optimal efficiency
Ensure durability of equipment
Minimize energy use