5.3001.5a
Sizing Ducts will be sized to deliver the appropriate amount of airflow (both supply and return) needed to satisfy the heating and/or cooling load of the building
Ducts will be sized using friction charts
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Manual D Residential Duct Systems or
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
equivalents will be used for all residential ductwork sizing
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Manual Q Low Pressure, Low Velocity Duct System Design or
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
equivalents will be used for all commercial ductwork sizing
Minimize static pressure
Maximize air flow
5.3001.5b
Air handler to return plenum Return plenum will be designed in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Manual D or equivalent
Radius elbow fittings or square fittings with turning vanes will be used to direct return air when a 90° turn is required
Minimize static pressure
Maximize air flow
5.3001.5c
Air handler to supply plenum Supply plenum will be designed in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Manual D or equivalent
Radius elbow fittings or square fittings with turning vanes will be installed to direct supply air
Supply plenum will be the same size as the air handler supply opening
Minimize static pressure
Maximize air flow
5.3001.5d
Building cavities used as ductwork Building cavities will not be used as ductwork in new systems
In existing systems, building cavities will be sealed and tested
Maximize air flow
Minimize energy use
Safeguard indoor air quality
5.3001.5e
Reducers Reducers between sections of different size ducts will be in accordance with existing standards based on duct material (
SMACNA
SMACNA
Sheet Metal and Air Conditioning Contractors' National Association, www.smacna.org
,
NAIMA
NAIMA
North American Insulation Manufacturers Association, www.naima.org
)
Minimize static pressure
Maximize air flow
5.3001.5f
Supply branch run outs Runs will be installed as short as possible
Minimize static pressure
Maximize air flow
5.3001.5g
Boots If using flexible duct with straight boots, duct will be connected to boot with no bend
A rigid elbow will be used when a flexible duct changes direction
A rigid connector will be used when joining two pieces of flexible duct together
Minimize static pressure
Maximize air flow
5.3001.5h
Supply terminations Terminations will be selected based on
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Manual T Air Distribution Basics
Minimize static pressure
Maximize air flow
5.3001.5i
Return grille sizing Terminations will be selected based on
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Manual T Air Distribution Basics
Grille gross area will be equal to or larger than return box
Minimize static pressure
Maximize air flow
5.3001.5j
Manual volume dampers Dampers will be installed as close to the trunk as possible while still being accessible to allow for adjustment after interior finishes are installed
Minimize static pressure and noise
Maximize air flow
5.3001.5k
Flexible ducts Flexible ducts will not be bent more than 45° without rigid elbow
Minimize static pressure
Maximize air flow
5.3001.5l
Take-offs Take-offs that create high turbulence will not be used (e.g., elbows with integrated dampers, scoops)
Take-offs will be installed onto the trunk in accordance with duct construction standards (
SMACNA
SMACNA
Sheet Metal and Air Conditioning Contractors' National Association, www.smacna.org
)
Minimize static pressure
Maximize air flow
5.3001.5m
Fire dampers Fire dampers shall be installed as required by applicable fire code
Minimize static pressure
Maximize air flow