3.1003.6a
Pre-inspection An inspection will be conducted for mold, water leaks, and water damage before sealing a dropped ceiling or soffit
Repairs will be completed before work begins
Repair moisture-related issues
3.1003.6b
Soffit general Air flow will be blocked at soffit in locations where access allows
Provide continuous
air barrier
Air barrier
The separation between the interior and exterior environments of a building that slows air flow to the point that no smoke movement is visible at 50 pascals of pressure difference across the boundary
across soffit openings
3.1003.6c
Option 1: bring soffit inside (seal at top) Entire opening will be spanned with
rigid material
Rigid material
Drywall, oriented strand board, duct board, cardboard, or any other stiff product that may support the load of insulation while serving as a durable air barrier
in line with the ceiling level
Material will be cut to fit and fastened as required
Prevent air leakage from wall to attic
Reduce opening to what can be sealed with sealant
Ensure closure is permanent and supports any load (e.g., wind, insulation)
Bring soffit into
thermal boundary
Thermal boundary
The separation between the interior and exterior environments of a building that slows heat flow
3.1003.6d
Option 2: leave soffit outside (seal at bottom or side) Each stud bay will be spanned with
rigid material
Rigid material
Drywall, oriented strand board, duct board, cardboard, or any other stiff product that may support the load of insulation while serving as a durable air barrier
will be cut to fit and fastened as required
OR
Backing at each stud bay will be provided and will be sealed
OR
Side of stud bays will be sealed with
rigid material
Rigid material
Drywall, oriented strand board, duct board, cardboard, or any other stiff product that may support the load of insulation while serving as a durable air barrier
from bottom of soffit to top-plate
OR
A sealed rigid barrier will be installed at all transitions
Prevent air leakage from wall to soffit
Reduce opening to what can be sealed with sealant
Ensure soffit is outside of the
thermal boundary
Thermal boundary
The separation between the interior and exterior environments of a building that slows heat flow
3.1003.6e
Soffits containing non-
IC
IC
Insulation contact
rated recessed lights Insulation will be kept at least 3" away from the top and side of any fixtures
If dropped soffit is to be filled with insulation, then a sealed rigid barrier enclosure will be installed to maintain a 3" clearance around the entire fixture
Top of rigid barrier enclosure will be sealed with non-insulating
rigid material
Rigid material
Drywall, oriented strand board, duct board, cardboard, or any other stiff product that may support the load of insulation while serving as a durable air barrier
(e.g., gypsum or equivalent
perm rating
Perm rating
The measurement of a material's ability to allow the transfer of water vapor through the material
and R-value)
Prevent light fixture from overheating
Bring light fixture inside of the
air barrier
Air barrier
The separation between the interior and exterior environments of a building that slows air flow to the point that no smoke movement is visible at 50 pascals of pressure difference across the boundary