| 5.3102.16b
Assess location for pump | System schematics, manufacturer specifications, and physical locations will be reviewed to identify proper and serviceable locations | Ensure proper placement of pump |
| 5.3102.16c
Install pump | When possible, pump will be installed in a physical location that is easy to access for maintenance purposes and in accordance with manufacturer specifications, paying special attention to the pump orientation Base-mounted pumps will be installed on concrete pads Base-mounted pumps will be connected to the system piping with vibration isolators Isolation valves, balance valves, strainers, pressure gauges, and motor starters/variable frequency drives (VFDs) will be installed in accordance with applicable specifications: SWS 5.3103.1 Balancing Valve Installation, SWS 5.3103.7 Instatllion of Pressure Gauges, SWS 5.3103.8 Isolation Valve Installation, SWS 5.3103.9 Installation of Strainers, SWS 5.3102.8 Replacement of Conventional Pumps with Electrically Commutated Motor-Drive Pumps (Hot Water), SWS 5.3102.9 Installation and Control of Variable Frequency Drives (Hot Water), SWS 5.3102.33 Optimize Varaiable Frequency Drive Control Other electrical devices and installation requirements will be in accordance with local codes and jurisdictions | Properly install pumping system |
| 5.3102.16d
Install redundant pumps | When possible, pump will be installed in a physical location that is easy to access for maintenance purposes and in accordance with manufacturer specifications, paying special attention to the pump orientation Base-mounted pumps will be installed on concrete pads Base-mounted pumps will be connected to the system piping with vibration isolators Isolation valves, balance valves, strainers, check valves, pressure gauges, and motor starters/VFDs will be installed in accordance with applicable specifications: SWS 5.3103.1 Balancing Valve Installation, SWS 5.3103.7 Installation of Pressure Guages, SWS 5.3.103.8 Isolation Valve Installation, SWS 5.3103.9 Installation of Strainers, SWS 5.3102.8 Replacement of Conventional Pumps with Electrically Commutated Motor-Driven Pumps (Hot Water), SWS 5.3102.9 Installation and Control of Variable Frequency Drives (Hot Water), SWS 5.3102.33 Optimize Variable Frequency Drive Control Isolation valves, balance valves, strainers, check valves, pressure gauges, and motor starters/VFDs will be installed in accordance with applicable specifications: SWS 5.3103.1 Balancing Valve Installation, SWS 5.3103.7 Installation of Pressure Guages, SWS 5.3.103.8 Isolation Valve Installation, SWS 5.3103.9 Installation of Strainers, SWS 5.3102.8 Replacement of Conventional Pumps with Electrically Commutated Motor-Driven Pumps (Hot Water), SWS 5.3102.9 Installation and Control of Variable Frequency Drives (Hot Water), SWS 5.3102.33 Optimize Variable Frequency Drive Control Lead-lag controls will be installed in accordance with SWS 5.3102.7 Installation of Lead Lag Controls - Pumps Other electrical devices and installation requirements will comply with local codes and jurisdictions | Properly install redundant pumping system |
| 5.3102.16e
Test pump | Water flow through the pump, head pressure, control sequences, operating amperage, and voltage shall be measured in accordance with
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ACCA
ACCA
Air Conditioning Contractors of America, www.acca.org
Standard 5 or
ANSI
ANSI
American National Standards Institute, www.ansi.org
/
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
Standard 111 and adjusted to meet design requirements Pump (and lead-lag controller, if applicable) will be started in accordance with manufacturer specifications Pump performance will be verified | Ensure proper operation of pumping equipment |
| 5.3102.16f
Insulate pump with removable and reusable insulation | Pump will be insulated with removable and renewable insulation to
IECC
IECC
International Energy Conservation Code
and
ASHRAE
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org
90.1, at a minimum | Reduce energy loss Maintain safe surface temperature |
| 5.3102.16g
Education | Completed work will be reviewed with the building/property management team and operations staff Building/property management team and operations staff will be educated on the safe and efficient operation and maintenance requirements of the installed item | Ensure building/property management team and operations staff is informed of the safe, efficient operation and maintenance requirements of the installed item |