FavoritePlease sign in to add this to your favorites. Topic: Whole Building Ventilation Subtopic: Exhaust-Only System Desired Outcome: Provide primary ventilation for common spaces Manufactured HousingPrintCopy to ExcelEmail TitleSpecification(s)Objective(s) 6.6205.1a Assessment Assessment will be done using ASHRAE ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org 62.2 standard: Blower door test Fan flow measurements Calculations Determine the ventilation needs of the whole house 6.6205.1b Selection Fan type will be capable of continuous operation and selected in accordance with ASHRAE ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org 62.2 for: Sizing Climate considerations Control strategy Sone rating DurabilityFan will be ENERGY STAR qualified Determine proper fan selectionMinimize energy consumption during fan operation 6.6205.1c Location No resistance greater than 3 pascals will exist between fan intake location with reference to the common area Ensure fresh air distribution to common areas 6.6205.1d Climate considerations ASHRAE ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers, www.ashrae.org 62.2 will be referenced for climate considerationsWhole house mechanical net exhaust flow for hot-humid climate will not exceed 7.5 cubic feet per minute/100 square feet Maintain building durabilityProtect occupant health 6.6205.1e Combustion Appliance Zone ( CAZ CAZ Combustion appliance zone ) testing CAZ CAZ Combustion appliance zone test will be performed where combustion appliances are utilized, where applicable Identify possible conditions that can cause unsafe equipment operating conditions 6.6205.1f Occupant education Occupant will be educated on: Purpose of the ventilation system Proper operation and use of controls Cost and benefit of system Manual shut offA label indicating the presence and purpose of the ventilation system will be included or a copy of the system operation guide will be posted at the electrical panelOperation guide or label will be permanently attached and in full sight Ensure occupant is educated on the safe and efficient operation of the systemDeliver intended air exchange 6.6205.1g Total exhaust airflow Total exhaust system airflow will be measured Ensure exhaust airflow is as designed Back to 6.6205 Exhaust-Only System Back to Top